Buck Boost Transformer Full Load Amps

Buck-Boost Transformers are small single phase isolation transformers that will reduce (Buck) or raise (Boost) line voltage when connected as an Autotransformer. The most common application is Boosting 208 to 230v. Two or three may be banked for three phase application where the neutral is available from the input.

Much smaller transformers may be used in Buck - Boost applications, since the size of the transformer is roughly proportional to the change in voltage. I.E.: A 10KVA load at 240v can be increased to 264v, a 10% change can be achieved with a 1KVA transformer.

Rating Voltage Change Table Transformer Multiplier Table
A1 A2 B1 B2 C1 C2 D1 D2 A1 A2 B1 B2 C1 C2 D1 D2
120/240 X 12/24 1.10 .90 1.20 .80 1.05 .95 1.10 .90 .10 .11 .20 .24 .05 .05 .10 .11
120/240 X 16/32 1.13 .87 1.27 .77 1.07 .93 1.13 .87 .13 .15 .27 .34 .07 .07 .13 .15
240/480 X 24/48 1.10 .90 1.20 .80 1.05 .95 1.10 .90 .10 .11 .20 .24 .05 .05 .10 .11
  1. Multiply Input voltage by the appropriate number in Voltage Change Table for output voltage.
  2. Multiply Load by the appropriate number in Transformer Multiplier Table for approximate transformer size.

A1: Boosting

A2: Bucking

B1: Boosting

B2: Bucking

C1: Boosting

C2: Bucking

D1: Boosting

D2: Bucking

 

Toll Free: (877-385-8624, Ph: (740) 385-8624 Fx: (740) 385-0024

8/30/21 We are in the process of upgrading servers. Email service will be disrupted during the cutover. Please use edgreenelectric@gmail.com or call or fax numbers below.

 

Corporate Office:

406 West 2nd Street
Logan, Ohio 43138

Ed Green Electric Map

Edge Logo
Hours: 8:00 AM to 5:00 PM M-F
24/7 Service Calls

Phone: 740-385-8624
Fax: 740-385-0024
Toll Free: 877-385-8624